Wire mesh tray, 100 mm height
Tray is made of medium carbon steel.
Coating - cold galvanizing.
Coating thickness ≥ 12µm.
Application scope - indoors.
Installation
Bends, risers, branches, crossings can be made directly from the straight sections of the mesh tray.
The installation of supports and (or) hangers for fastening the trays should be calculated based on the expected load and can reach 2.5 m.
Operating temperature of cable trays is from -40°C to +150°C.
Choice of tray size by number of cables
The height of the wire mesh tray must not be less than the diameter of the thickest cable when laid in one layer or the sum of the diameters of cables laid in several layers. Tray width is selected to accommodate the required number of cables plus a margin for expanding number of cables. When choosing the dimensions of the tray, it is also necessary to consider the requirements of regulatory documents, for example, clause 2.1.61 of the PUE states: "in trunking, wires and cables can be neatly dressed or randomly laid in layers. The sum of the cross sections of wires and cables calculated from their outer diameters, including insulation and outer jackets, should not exceed: 35% of the cross section of the conduit; 45% for the trunking with opening lid."
Installation Instructions
Wire mesh tray, 100 mm height LAN-MT100xxxx-3.8EZ
-
Suspend the tray
Install the tray on the specified ceiling supports and check that the support spacing suits the project design.
-
Join straight sections
Locate adjacent sections with their formed ends and lock each joint with the connecting clips shown in the video.
-
Form bends and branches
Arrange straight sections into the required route. Use the illustrated connecting hardware for bends, branches and changes of direction.
-
Fix the tray to supports
Attach the tray to support profiles, wall brackets or suspended supports with the retaining clips suitable for the selected tray width.
-
Route and protect cables
Route cables along the completed tray, keep bends smooth, and use a suitable roller or edge protection wherever a cable passes over the tray edge.
-
Check the completed route
Verify that every section and support is secure, the cable route is continuous, and the tray is supported at transitions and cabinet entries.
Package dimensions and weight
Single item
| Product code | Unit | length × width × height (mm) | Weight (kg) | Volume (m3) |
|---|---|---|---|---|
| LAN-MT100x100-3.8EZ | pcs | 3000 × 115 × 110 | 3.2 | 0.03795 |
| LAN-MT100x150-3.8EZ | pcs | 3000 × 165 × 110 | 1.8 | 0.05445 |
| LAN-MT100x200-3.8EZ | pcs | 3000 × 215 × 110 | 4.2 | 0.07095 |
| LAN-MT100x300-3.8EZ | pcs | 3000 × 315 × 110 | 5 | 0.10395 |
| LAN-MT100x400-3.8EZ | pcs | 3000 × 415 × 110 | 5 | 0.13695 |